Airtec® HydroSens AHU  Duct Humidification

Airtec® HydroSens AHU HAVAC Humidification

Adiabatic modular high-pressure nozzle system for duct and exhaust air cooling, designed according to VDI 6022. Designed for lowest power consumption at very high efficiency and low water loss by a frequency-controlled high-pressure atomization.
The system contains only inert components. The hygiene concept waived in accordance with VDI 6022 on stationary or circulating water as well as porous, water-storing elements.
The high-pressure nozzle system works without any chemical or biological additives. Regular, consuming and costly monitoring and metered disinfectants is completely eliminated by the hygienic concept and unique design.

System construction

Specifications

1 system for 2 + 1 channel systems:

  • Control and pump on one console
  • PLC control and clear display
  • for each HAVAC unit 3 solenoid valves, allow an exact 7-step cascade control
  • Pump performance 4 to 600 l/h, 24 to 800 l/h, 48 to 1200 l/h.
  • Frequency-controlled high pressure pump system
  • Hygienic flushing system
  • Flow control
  • Stainless steel nozzle rack with fixing elements
  • Stainless steel nozzles 2.7 / 4.0 / 5.2 kg/h with integrated "non-return-valve" and "anti-drop function"
  • Inorganic ceramic double evaporation droplet separator hygienically certified according to VDI6022 with lowest pressure loss
  • The efficiency of the evaporator module is 95% at air velocities of 1-3 m / s
  • Manufactured and certified according to VDI 6022, ISO 9001, ISO 14001 and ISO 22000 HACCP
  • Space-saving, minimum distance between nozzle and droplet separator <1m
  • Easy and cost-effective installation and maintenance
  • Ethernet module Modbus, MySql or RS485
  • Datalog system for data analysis

 

Option:

  • Remote control via Scada software
  • Extension rate to 3rd chamber
  • Inert reaction chamber according to our specifications related to the VDI 6022 on-site, or as an optional service depending on specification.